Certify66
← Back to Maintenance Practices
Section 7.7

EWIS, Electrical Wiring Interconnection System

Continuity, insulation and bonding testing; crimping and crimp inspection; connectors, looming, clamping, routing, and the separation and segregation of cables.

Notes

EWIS, summary notes

Main ideas
  • EWIS covers the wires, connectors, terminations, looms, clamps and bonding that carry power and signals around the aircraft, and the practices that keep them serviceable.
  • A crimped termination joins conductor to terminal by controlled deformation. Select the terminal for the wire gauge and stud size, strip without nicking strands, insert fully so bare wire shows in the inspection window, and crimp with a calibrated tool and the matching die. The ratchet prevents release until the crimp is complete.
  • Crimp inspection: correct terminal and tool, crimp central and fully formed, insulation gripped where required, no cut or protruding strands, and a pull test where specified.
  • Bonding connects metallic parts to a common low-resistance reference. It dissipates static, gives lightning and fault currents a safe path, prevents arcing and provides a stable earth reference. Bonds are measured in milliohms, and mating faces are cleaned to bare metal then re-protected against corrosion.
  • Continuity testing proves a circuit is complete; insulation testing proves conductors are not leaking to each other or to earth. Insulation testers must not be applied to solid-state equipment.
  • Routing and protection: respect minimum bend radii, clamp at the specified intervals, avoid chafing against structure, keep clear of hot areas and moving parts, and provide a drip loop so fluid runs off rather than into a connector.
  • Separation and segregation keep power cables away from sensitive signal and screened cables so interference is not induced, and keep redundant system channels physically apart so one event cannot take out both.
  • ⚠ Exam trap: bonding is tested for LOW RESISTANCE in milliohms, not for tensile strength or continuity alone.
Key formulas
Bonding resistance
measured in milliohms, check the AMM figure
Crimp check
correct die · full barrel · insulation gripped · no cut strands · pull test
Separation
power away from signal · redundant channels physically apart
Solved examples
  1. A crimped terminal passes a visual check but pulls off the wire under a light load. What was most likely wrong?

    The wrong die or terminal for the wire gauge, so the barrel was never fully compressed onto the conductor. A crimp that looks acceptable but has not been formed with the matching calibrated tool will not develop its designed mechanical grip.

  2. Why are the two channels of a redundant system routed on opposite sides of the fuselage?

    So that a single local event, a fire, a burst duct, structural damage or chafing at one clamp, cannot damage both channels at once. Physical separation is what makes the redundancy real rather than nominal.

Mind map

EWIS concept map

EWIS

Quiz

EWIS quiz

EWIS, quiz

Ref 7.712 of 16Pass 75%
  1. 1. Bonding in EWIS is primarily tested for:

    Electrical continuity and low resistance
    Tensile strength
    Colour coding
  2. 2. Bonding resistance is measured in:

    Milliohms
    Megohms
    Kilohms
  3. 3. The purposes of bonding include:

    Static dissipation and a safe path for lightning and fault current
    Increasing the structural strength of the joint by tying the two members together electrically
    Reducing cable weight, since a bonded structure can serve as the return path for every circuit
  4. 4. When making a crimped connection the conductor must be:

    Fully inserted, with bare wire visible in the inspection window
    Inserted half way
    Left slightly short of the barrel
  5. 5. Insulation must be stripped:

    Without nicking or severing strands
    By burning it off
    With side cutters
  6. 6. The ratchet on a crimp tool:

    Prevents release until a full crimp is formed
    Speeds the operation
    Measures the wire gauge
  7. 7. A crimp inspection includes checking that:

    No strands are cut or protruding and the crimp is central
    The wire is warm
    The terminal is painted
  8. 8. Bonding surfaces are prepared by:

    Cleaning to bare metal, then re-protecting after connection
    Painting before assembly
    Applying grease
  9. 9. Power cables are separated from sensitive signal cables to:

    Prevent induced interference
    Save weight
    Simplify the loom
  10. 10. Redundant system channels are routed apart so that:

    A single local event cannot damage both
    The looms are easier to build
    Voltage drop is reduced
  11. 11. A drip loop in a cable run is provided so that:

    Fluid runs off rather than into the connector
    The cable can stretch
    The loom looks tidy
  12. 12. Continuity testing proves:

    The circuit path is complete
    The insulation is sound
    The bonding is adequate